Wiring: | 3P+N/4P three-phase four-wire system | |
1P+N/2P single phase | ||
Rated Operating Voltage (Un): | 3P+N/4P 400V AC / 50Hz | |
1P+N/2P 230V AC / 50Hz | ||
Undervoltage protection value | 161V±5V (recovery value: 195V±5V) (phase voltage) | |
Overvoltage protection value | 275V±5V (Recovery value: 253V±5V) (phase voltage) | |
Self-recovery closing delay | T3=20~60s | |
Dielectric Strength: | 2500VAC for 1 min | |
Withstand Voltage Level (UIMP): | 4KV | |
Mechanical Life: | 10000 times, 3 times/min | |
Action time: | Opening ≤ 0.2s, Closing ≤ 0.5s (excluding delay) | |
Ingress Protection: | IP20 | |
Operating Temperature: | -25℃~60℃ | |
Relative humidity of the air: | ≤95%(55℃) | |
Action process: | If the voltage is detected to exceed the under-voltage protection value or the over-voltage protection value, it will be opened after the fixed opening delay, and when the voltage is restored, it will be automatically closed after the fixed self-recovery closing delay. | |
Communication: | Standard RS485 communication interface, which can realize remote control, and can be intelligently managed such as opening, closing and querying operation status from a long distance (if this function is available) | |
Manual/Automatic Operation: | Dial [Manual/Auto] to automatic mode, except for automatic action due to voltage failure, such as manually opening the circuit breaker or tripping the switch due to load failure, it will not automatically reclose, and it needs to be manually closed and reset (other faults that may exist need to be manually eliminated) | |
If you dial [Manual/Auto] to manual mode, you can manually open or close without automatic action | ||
Safety padlocks: | When the opening state can be padlocked, the lock diameter is Φ4mm, and the product cannot be closed after padlock (keep tripping) | |
Light: | Solid green: normal operation, closing status | |
Solid red: Undervoltage fault | ||
Flashing red: Overvoltage fault | ||
Flashing green: Delayed closing | ||
Solid orange: Fault latching | ||
Indicator light off: There is no power or the [Manual/Auto] switch is in manual state. |
![]() |