Rated Operating Voltage (Uc): | 1P+N 230V AC / 50Hz | |
Dielectric Strength: | 2500VAC for 1 min | |
Withstand Voltage Level (UIMP): | 6KV | |
Mechanical Life: | 10000 times, 3 times/min | |
Action time: | Opening ≤ 2s, closing ≤ 3s | |
Ingress Protection: | IP20 | |
Operating Temperature: | -25℃~60℃ | |
Relative humidity of the air: | ≤95%(55℃) | |
Action process: | In the automatic state, the remote control opens and closes | |
Manual/Automatic Operation: | Dial [Manual/Auto] to automatic mode to remotely control opening and closing | |
Turn [Manual/Auto] to manual mode, and the remote control will be disabled | ||
Light: | Solid green: automatic status; Flashing green: manual status; Indicator light off: no power supply; Constant red light: over-voltage and under-voltage protection; Flashing red: leakage protection; Orange light is always on: overload protection, short circuit protection; Flashing orange: Temperature protection | |
Monitoring features: refer to the attachment communication protocol for details | ||
Leakage current monitoring function | The measurement range of leakage current is 1mA~1000mA, and the measurement accuracy is not less than 3mA (range 1~200mA) and 2% (200mA~1A) | |
Current monitoring function | Real-time detection of current in the line with an accuracy of 0.1A | |
Voltage monitoring function | Real-time monitoring of line voltage, the measurement range is 132V~320V, and the error is not more than 1%. | |
Temperature monitoring function | The internal temperature of the MCU on the circuit board shall not exceed 5 degrees. The measurement range is -20~120 degrees | |
Frequency monitoring function | Real-time monitoring of line frequency, range 20Hz~80Hz. | |
Active power monitoring function | Real-time monitoring of line active power | |
Total energy monitoring function | Real-time monitoring of total line energy (single phase) |