| Basic parameters | ||||||
| 1 | Product standards | - | GB/T 14048.3 | |||
| 2 | Shell frame grade | A | 125 | |||
| 3 | Number of poles | - | 1P、2P、3P、4P | |||
| 4 | Rated current In | A | 16、20、32、40、50、63、80、100、125 | |||
| 5 | Rated voltage UE | V | [AC 230V]-(1P、2P); [AC 400V]-(2P、3P、4P) | |||
| 6 | Rated frequency | Hz | 50/60 | |||
| 7 | Rated insulation voltage UI | V | AC 1000 | |||
| 8 | Rated impulse withstand voltage (Uimp) | kV | 6 | |||
| 9 | Rated short-time withstand current ICW | A/1s | 20Ie | |||
| 10 | Rated short-circuit turn-on capability Icm | A, peak | 20Ie | |||
| 11 | Use categories | - | AC-23A | |||
| 12 | Ingress protection | - | IP20 | |||
| 13 | Wiring capacity | mm² | ≤50 | |||
| Operational performance (times) | ||||||
| 14 | The number of cycles of no-current operation | times | 15000 | |||
| 15 | The number of cycles of on-current operation | times | 6000 | |||