| Basic parameters | ||||||
| 1 | Product standards | - | GB/T 16917.1 and GB/T 22794 (Type B) | |||
| 2 | Trip curve | - | B(3In-5In); C (5In-10In); D (10In-20In) | |||
| 3 | Number of poles | - | 1P+N、2P、3P、3P+N、4P | |||
| 4 | Rated current In | A | 1、2、3、4、5、6、10、16、20、25、32、40、50、63 | |||
| 5 | Rated residual operating current | A | 30mA、50mA、100mA、300mA | |||
| 6 | Residual current protection type and method | - | Electronic, AC type/A/B type, general type/time-delay type | |||
| 7 | Rated voltage UE | V | 1P+N、2P:230V~; 3P、3P+N、4P:400V~ | |||
| 8 | Rated insulation voltage | V | 500 | |||
| 9 | Rated frequency | Hz | 50/60 | |||
| 10 | Breaking capacity | kA | 6 | |||
| 11 | Rated impulse withstand voltage (Uimp) | kV | 4 | |||
| 12 | Reference temperature | ℃ | 30 | |||
| 13 | Pollution level | - | 2 | |||
| 14 | Ingress protection | - | IP20 | |||
| 15 | Wiring capacity | mm² | >32A: hard conductor≤25; Flexible conductor ≤16≤32A: hard conductor ≤16; Flexible wire ≤ 10 | |||
| Operational performance | ||||||
| 16 | Mechanical life | times | 20000 | |||
| 17 | Electrical life | times | 10000 | |||