Basic parameters | ||||||
1 | Product standards | - | GB/T 16917.1 and GB/T 22794 (Type B) | |||
2 | Trip curve | - | B(3In-5In); C (5In-10In); D (10In-20In) | |||
3 | Number of poles | - | 1P+N、2P、3P、3P+N、4P | |||
4 | Rated current In | A | 1、2、3、4、5、6、10、16、20、25、32、40、50、63 | |||
5 | Rated residual operating current | A | 30mA、50mA、100mA、300mA | |||
6 | Residual current protection type and method | - | Electronic, AC type/A/B type, general type/time-delay type | |||
7 | Rated voltage UE | V | 1P+N、2P:230V~; 3P、3P+N、4P:400V~ | |||
8 | Rated insulation voltage | V | 500 | |||
9 | Rated frequency | Hz | 50/60 | |||
10 | Breaking capacity | kA | 6 | |||
11 | Rated impulse withstand voltage (Uimp) | kV | 4 | |||
12 | Reference temperature | ℃ | 30 | |||
13 | Pollution level | - | 2 | |||
14 | Ingress protection | - | IP20 | |||
15 | Wiring capacity | mm² | >32A: hard conductor≤25; Flexible conductor ≤16≤32A: hard conductor ≤16; Flexible wire ≤ 10 | |||
Operational performance | ||||||
16 | Mechanical life | times | 20000 | |||
17 | Electrical life | times | 10000 |