| Parameters and characteristics | description | |
| Number of poles | 2P | |
| Rated operating voltage Ue | 230V | |
| frequency | 50Hz | |
| Rated insulation voltage Ui | 500V | |
| Rated impulse withstand voltage Uimp | 6kV | |
| Rated operating current In | 6A~63A | |
| Rated short-circuit capability ICN | 6kA | |
| Instantaneous trip type | Type C | |
| Tripper type | Thermomagnetic | |
| Mechanical life | 10000 times | |
| Electrical life | 4000 times | |
| Overload protection | Electronic (non-double gold) | |
| correspondence | It has Bluetooth communication interface, RS485 communication interface and HPLC communication interface, and can collect the status and information of the energy meter through the above communication interface | |
| Communication protocols | Comply with the requirements of DL/T 698.45 "Power Information Acquisition and Management System Part 4-5: Communication Protocols - Object-Oriented Data Exchange Protocols". | |
| Overvoltage and undervoltage alarm and threshold protection | Over-voltage protection range value: 255V~360V, under-voltage protection range value: 50V~180V, over-voltage recovery value: 250±5V, under-voltage recovery value: 165±5V, all alarm values, opening thresholds, and setting time can be set | |
| Overload alarm and threshold protection | Protection range value: 100%~130% | |
| Over-temperature alarm and threshold protection | Protection range value: -40°C~120°C, detection accuracy meets ±10°C | |
| power consumption | Not more than 2W | |
| Metrological accuracy | The active work is greater than or equal to grade B | |
| Neutral current monitoring | The measuring range is Imin~1.2Imax, and the quotation error is not more than ±2% | |
| Leakage monitoring | The measuring range is 10mA~1000mA, and the residual current deviation of the measurement is not more than 5mA | |
| Ingress protection | IP20 | |
| Pollution level | Level 2 | |
| Operating ambient temperature | -25℃~+60℃ | |
| Store ambient air temperature | -40℃~+70℃ | |
| Relative humidity of the air | ≤90%(55℃) | |
| Installation: | It is installed with TH35mm standard mounting rails | |
| Light | Red indicator: Pulse indication | |
| Yellow indicator: Open indication | ||
| Two-color light: the green light is always on during normal operation, and the red light is always on when there is an alarm | ||
| Indicator light off: No power | ||
| keystroke | Page turn button | |
| The opening action test button |